1	Power allocator governor tunables
2	=================================
3	
4	Trip points
5	-----------
6	
7	The governor works optimally with the following two passive trip points:
8	
9	1.  "switch on" trip point: temperature above which the governor
10	    control loop starts operating.  This is the first passive trip
11	    point of the thermal zone.
12	
13	2.  "desired temperature" trip point: it should be higher than the
14	    "switch on" trip point.  This the target temperature the governor
15	    is controlling for.  This is the last passive trip point of the
16	    thermal zone.
17	
18	PID Controller
19	--------------
20	
21	The power allocator governor implements a
22	Proportional-Integral-Derivative controller (PID controller) with
23	temperature as the control input and power as the controlled output:
24	
25	    P_max = k_p * e + k_i * err_integral + k_d * diff_err + sustainable_power
26	
27	where
28	    e = desired_temperature - current_temperature
29	    err_integral is the sum of previous errors
30	    diff_err = e - previous_error
31	
32	It is similar to the one depicted below:
33	
34	                                      k_d
35	                                       |
36	current_temp                           |
37	     |                                 v
38	     |                +----------+   +---+
39	     |         +----->| diff_err |-->| X |------+
40	     |         |      +----------+   +---+      |
41	     |         |                                |      tdp        actor
42	     |         |                      k_i       |       |  get_requested_power()
43	     |         |                       |        |       |        |     |
44	     |         |                       |        |       |        |     | ...
45	     v         |                       v        v       v        v     v
46	   +---+       |      +-------+      +---+    +---+   +---+   +----------+
47	   | S |-------+----->| sum e |----->| X |--->| S |-->| S |-->|power     |
48	   +---+       |      +-------+      +---+    +---+   +---+   |allocation|
49	     ^         |                                ^             +----------+
50	     |         |                                |                |     |
51	     |         |        +---+                   |                |     |
52	     |         +------->| X |-------------------+                v     v
53	     |                  +---+                               granted performance
54	desired_temperature       ^
55	                          |
56	                          |
57	                      k_po/k_pu
58	
59	Sustainable power
60	-----------------
61	
62	An estimate of the sustainable dissipatable power (in mW) should be
63	provided while registering the thermal zone.  This estimates the
64	sustained power that can be dissipated at the desired control
65	temperature.  This is the maximum sustained power for allocation at
66	the desired maximum temperature.  The actual sustained power can vary
67	for a number of reasons.  The closed loop controller will take care of
68	variations such as environmental conditions, and some factors related
69	to the speed-grade of the silicon.  `sustainable_power` is therefore
70	simply an estimate, and may be tuned to affect the aggressiveness of
71	the thermal ramp. For reference, the sustainable power of a 4" phone
72	is typically 2000mW, while on a 10" tablet is around 4500mW (may vary
73	depending on screen size).
74	
75	If you are using device tree, do add it as a property of the
76	thermal-zone.  For example:
77	
78		thermal-zones {
79			soc_thermal {
80				polling-delay = <1000>;
81				polling-delay-passive = <100>;
82				sustainable-power = <2500>;
83				...
84	
85	Instead, if the thermal zone is registered from the platform code, pass a
86	`thermal_zone_params` that has a `sustainable_power`.  If no
87	`thermal_zone_params` were being passed, then something like below
88	will suffice:
89	
90		static const struct thermal_zone_params tz_params = {
91			.sustainable_power = 3500,
92		};
93	
94	and then pass `tz_params` as the 5th parameter to
95	`thermal_zone_device_register()`
96	
97	k_po and k_pu
98	-------------
99	
100	The implementation of the PID controller in the power allocator
101	thermal governor allows the configuration of two proportional term
102	constants: `k_po` and `k_pu`.  `k_po` is the proportional term
103	constant during temperature overshoot periods (current temperature is
104	above "desired temperature" trip point).  Conversely, `k_pu` is the
105	proportional term constant during temperature undershoot periods
106	(current temperature below "desired temperature" trip point).
107	
108	These controls are intended as the primary mechanism for configuring
109	the permitted thermal "ramp" of the system.  For instance, a lower
110	`k_pu` value will provide a slower ramp, at the cost of capping
111	available capacity at a low temperature.  On the other hand, a high
112	value of `k_pu` will result in the governor granting very high power
113	whilst temperature is low, and may lead to temperature overshooting.
114	
115	The default value for `k_pu` is:
116	
117	    2 * sustainable_power / (desired_temperature - switch_on_temp)
118	
119	This means that at `switch_on_temp` the output of the controller's
120	proportional term will be 2 * `sustainable_power`.  The default value
121	for `k_po` is:
122	
123	    sustainable_power / (desired_temperature - switch_on_temp)
124	
125	Focusing on the proportional and feed forward values of the PID
126	controller equation we have:
127	
128	    P_max = k_p * e + sustainable_power
129	
130	The proportional term is proportional to the difference between the
131	desired temperature and the current one.  When the current temperature
132	is the desired one, then the proportional component is zero and
133	`P_max` = `sustainable_power`.  That is, the system should operate in
134	thermal equilibrium under constant load.  `sustainable_power` is only
135	an estimate, which is the reason for closed-loop control such as this.
136	
137	Expanding `k_pu` we get:
138	    P_max = 2 * sustainable_power * (T_set - T) / (T_set - T_on) +
139	        sustainable_power
140	
141	where
142	    T_set is the desired temperature
143	    T is the current temperature
144	    T_on is the switch on temperature
145	
146	When the current temperature is the switch_on temperature, the above
147	formula becomes:
148	
149	    P_max = 2 * sustainable_power * (T_set - T_on) / (T_set - T_on) +
150	        sustainable_power = 2 * sustainable_power + sustainable_power =
151	        3 * sustainable_power
152	
153	Therefore, the proportional term alone linearly decreases power from
154	3 * `sustainable_power` to `sustainable_power` as the temperature
155	rises from the switch on temperature to the desired temperature.
156	
157	k_i and integral_cutoff
158	-----------------------
159	
160	`k_i` configures the PID loop's integral term constant.  This term
161	allows the PID controller to compensate for long term drift and for
162	the quantized nature of the output control: cooling devices can't set
163	the exact power that the governor requests.  When the temperature
164	error is below `integral_cutoff`, errors are accumulated in the
165	integral term.  This term is then multiplied by `k_i` and the result
166	added to the output of the controller.  Typically `k_i` is set low (1
167	or 2) and `integral_cutoff` is 0.
168	
169	k_d
170	---
171	
172	`k_d` configures the PID loop's derivative term constant.  It's
173	recommended to leave it as the default: 0.
174	
175	Cooling device power API
176	========================
177	
178	Cooling devices controlled by this governor must supply the additional
179	"power" API in their `cooling_device_ops`.  It consists on three ops:
180	
181	1. int get_requested_power(struct thermal_cooling_device *cdev,
182		struct thermal_zone_device *tz, u32 *power);
183	@cdev: The `struct thermal_cooling_device` pointer
184	@tz: thermal zone in which we are currently operating
185	@power: pointer in which to store the calculated power
186	
187	`get_requested_power()` calculates the power requested by the device
188	in milliwatts and stores it in @power .  It should return 0 on
189	success, -E* on failure.  This is currently used by the power
190	allocator governor to calculate how much power to give to each cooling
191	device.
192	
193	2. int state2power(struct thermal_cooling_device *cdev, struct
194	        thermal_zone_device *tz, unsigned long state, u32 *power);
195	@cdev: The `struct thermal_cooling_device` pointer
196	@tz: thermal zone in which we are currently operating
197	@state: A cooling device state
198	@power: pointer in which to store the equivalent power
199	
200	Convert cooling device state @state into power consumption in
201	milliwatts and store it in @power.  It should return 0 on success, -E*
202	on failure.  This is currently used by thermal core to calculate the
203	maximum power that an actor can consume.
204	
205	3. int power2state(struct thermal_cooling_device *cdev, u32 power,
206		unsigned long *state);
207	@cdev: The `struct thermal_cooling_device` pointer
208	@power: power in milliwatts
209	@state: pointer in which to store the resulting state
210	
211	Calculate a cooling device state that would make the device consume at
212	most @power mW and store it in @state.  It should return 0 on success,
213	-E* on failure.  This is currently used by the thermal core to convert
214	a given power set by the power allocator governor to a state that the
215	cooling device can set.  It is a function because this conversion may
216	depend on external factors that may change so this function should the
217	best conversion given "current circumstances".
218	
219	Cooling device weights
220	----------------------
221	
222	Weights are a mechanism to bias the allocation among cooling
223	devices.  They express the relative power efficiency of different
224	cooling devices.  Higher weight can be used to express higher power
225	efficiency.  Weighting is relative such that if each cooling device
226	has a weight of one they are considered equal.  This is particularly
227	useful in heterogeneous systems where two cooling devices may perform
228	the same kind of compute, but with different efficiency.  For example,
229	a system with two different types of processors.
230	
231	If the thermal zone is registered using
232	`thermal_zone_device_register()` (i.e., platform code), then weights
233	are passed as part of the thermal zone's `thermal_bind_parameters`.
234	If the platform is registered using device tree, then they are passed
235	as the `contribution` property of each map in the `cooling-maps` node.
236	
237	Limitations of the power allocator governor
238	===========================================
239	
240	The power allocator governor's PID controller works best if there is a
241	periodic tick.  If you have a driver that calls
242	`thermal_zone_device_update()` (or anything that ends up calling the
243	governor's `throttle()` function) repetitively, the governor response
244	won't be very good.  Note that this is not particular to this
245	governor, step-wise will also misbehave if you call its throttle()
246	faster than the normal thermal framework tick (due to interrupts for
247	example) as it will overreact.