1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281
=================================
Power allocator governor tunables
=================================

Trip points
-----------

The governor works optimally with the following two passive trip points:

1.  "switch on" trip point: temperature above which the governor
    control loop starts operating.  This is the first passive trip
    point of the thermal zone.

2.  "desired temperature" trip point: it should be higher than the
    "switch on" trip point.  This the target temperature the governor
    is controlling for.  This is the last passive trip point of the
    thermal zone.

PID Controller
--------------

The power allocator governor implements a
Proportional-Integral-Derivative controller (PID controller) with
temperature as the control input and power as the controlled output:

    P_max = k_p * e + k_i * err_integral + k_d * diff_err + sustainable_power

where
   -  e = desired_temperature - current_temperature
   -  err_integral is the sum of previous errors
   -  diff_err = e - previous_error

It is similar to the one depicted below::

				      k_d
				       |
  current_temp                         |
       |                               v
       |              +----------+   +---+
       |       +----->| diff_err |-->| X |------+
       |       |      +----------+   +---+      |
       |       |                                |      tdp        actor
       |       |                      k_i       |       |  get_requested_power()
       |       |                       |        |       |        |     |
       |       |                       |        |       |        |     | ...
       v       |                       v        v       v        v     v
     +---+     |      +-------+      +---+    +---+   +---+   +----------+
     | S |-----+----->| sum e |----->| X |--->| S |-->| S |-->|power     |
     +---+     |      +-------+      +---+    +---+   +---+   |allocation|
       ^       |                                ^             +----------+
       |       |                                |                |     |
       |       |        +---+                   |                |     |
       |       +------->| X |-------------------+                v     v
       |                +---+                               granted performance
  desired_temperature     ^
			  |
			  |
		      k_po/k_pu

Sustainable power
-----------------

An estimate of the sustainable dissipatable power (in mW) should be
provided while registering the thermal zone.  This estimates the
sustained power that can be dissipated at the desired control
temperature.  This is the maximum sustained power for allocation at
the desired maximum temperature.  The actual sustained power can vary
for a number of reasons.  The closed loop controller will take care of
variations such as environmental conditions, and some factors related
to the speed-grade of the silicon.  `sustainable_power` is therefore
simply an estimate, and may be tuned to affect the aggressiveness of
the thermal ramp. For reference, the sustainable power of a 4" phone
is typically 2000mW, while on a 10" tablet is around 4500mW (may vary
depending on screen size). It is possible to have the power value
expressed in an abstract scale. The sustained power should be aligned
to the scale used by the related cooling devices.

If you are using device tree, do add it as a property of the
thermal-zone.  For example::

	thermal-zones {
		soc_thermal {
			polling-delay = <1000>;
			polling-delay-passive = <100>;
			sustainable-power = <2500>;
			...

Instead, if the thermal zone is registered from the platform code, pass a
`thermal_zone_params` that has a `sustainable_power`.  If no
`thermal_zone_params` were being passed, then something like below
will suffice::

	static const struct thermal_zone_params tz_params = {
		.sustainable_power = 3500,
	};

and then pass `tz_params` as the 5th parameter to
`thermal_zone_device_register()`

k_po and k_pu
-------------

The implementation of the PID controller in the power allocator
thermal governor allows the configuration of two proportional term
constants: `k_po` and `k_pu`.  `k_po` is the proportional term
constant during temperature overshoot periods (current temperature is
above "desired temperature" trip point).  Conversely, `k_pu` is the
proportional term constant during temperature undershoot periods
(current temperature below "desired temperature" trip point).

These controls are intended as the primary mechanism for configuring
the permitted thermal "ramp" of the system.  For instance, a lower
`k_pu` value will provide a slower ramp, at the cost of capping
available capacity at a low temperature.  On the other hand, a high
value of `k_pu` will result in the governor granting very high power
while temperature is low, and may lead to temperature overshooting.

The default value for `k_pu` is::

    2 * sustainable_power / (desired_temperature - switch_on_temp)

This means that at `switch_on_temp` the output of the controller's
proportional term will be 2 * `sustainable_power`.  The default value
for `k_po` is::

    sustainable_power / (desired_temperature - switch_on_temp)

Focusing on the proportional and feed forward values of the PID
controller equation we have::

    P_max = k_p * e + sustainable_power

The proportional term is proportional to the difference between the
desired temperature and the current one.  When the current temperature
is the desired one, then the proportional component is zero and
`P_max` = `sustainable_power`.  That is, the system should operate in
thermal equilibrium under constant load.  `sustainable_power` is only
an estimate, which is the reason for closed-loop control such as this.

Expanding `k_pu` we get::

    P_max = 2 * sustainable_power * (T_set - T) / (T_set - T_on) +
	sustainable_power

where:

    - T_set is the desired temperature
    - T is the current temperature
    - T_on is the switch on temperature

When the current temperature is the switch_on temperature, the above
formula becomes::

    P_max = 2 * sustainable_power * (T_set - T_on) / (T_set - T_on) +
	sustainable_power = 2 * sustainable_power + sustainable_power =
	3 * sustainable_power

Therefore, the proportional term alone linearly decreases power from
3 * `sustainable_power` to `sustainable_power` as the temperature
rises from the switch on temperature to the desired temperature.

k_i and integral_cutoff
-----------------------

`k_i` configures the PID loop's integral term constant.  This term
allows the PID controller to compensate for long term drift and for
the quantized nature of the output control: cooling devices can't set
the exact power that the governor requests.  When the temperature
error is below `integral_cutoff`, errors are accumulated in the
integral term.  This term is then multiplied by `k_i` and the result
added to the output of the controller.  Typically `k_i` is set low (1
or 2) and `integral_cutoff` is 0.

k_d
---

`k_d` configures the PID loop's derivative term constant.  It's
recommended to leave it as the default: 0.

Cooling device power API
========================

Cooling devices controlled by this governor must supply the additional
"power" API in their `cooling_device_ops`.  It consists on three ops:

1. ::

    int get_requested_power(struct thermal_cooling_device *cdev,
			    struct thermal_zone_device *tz, u32 *power);


@cdev:
	The `struct thermal_cooling_device` pointer
@tz:
	thermal zone in which we are currently operating
@power:
	pointer in which to store the calculated power

`get_requested_power()` calculates the power requested by the device
in milliwatts and stores it in @power .  It should return 0 on
success, -E* on failure.  This is currently used by the power
allocator governor to calculate how much power to give to each cooling
device.

2. ::

	int state2power(struct thermal_cooling_device *cdev, struct
			thermal_zone_device *tz, unsigned long state,
			u32 *power);

@cdev:
	The `struct thermal_cooling_device` pointer
@tz:
	thermal zone in which we are currently operating
@state:
	A cooling device state
@power:
	pointer in which to store the equivalent power

Convert cooling device state @state into power consumption in
milliwatts and store it in @power.  It should return 0 on success, -E*
on failure.  This is currently used by thermal core to calculate the
maximum power that an actor can consume.

3. ::

	int power2state(struct thermal_cooling_device *cdev, u32 power,
			unsigned long *state);

@cdev:
	The `struct thermal_cooling_device` pointer
@power:
	power in milliwatts
@state:
	pointer in which to store the resulting state

Calculate a cooling device state that would make the device consume at
most @power mW and store it in @state.  It should return 0 on success,
-E* on failure.  This is currently used by the thermal core to convert
a given power set by the power allocator governor to a state that the
cooling device can set.  It is a function because this conversion may
depend on external factors that may change so this function should the
best conversion given "current circumstances".

Cooling device weights
----------------------

Weights are a mechanism to bias the allocation among cooling
devices.  They express the relative power efficiency of different
cooling devices.  Higher weight can be used to express higher power
efficiency.  Weighting is relative such that if each cooling device
has a weight of one they are considered equal.  This is particularly
useful in heterogeneous systems where two cooling devices may perform
the same kind of compute, but with different efficiency.  For example,
a system with two different types of processors.

If the thermal zone is registered using
`thermal_zone_device_register()` (i.e., platform code), then weights
are passed as part of the thermal zone's `thermal_bind_parameters`.
If the platform is registered using device tree, then they are passed
as the `contribution` property of each map in the `cooling-maps` node.

Limitations of the power allocator governor
===========================================

The power allocator governor's PID controller works best if there is a
periodic tick.  If you have a driver that calls
`thermal_zone_device_update()` (or anything that ends up calling the
governor's `throttle()` function) repetitively, the governor response
won't be very good.  Note that this is not particular to this
governor, step-wise will also misbehave if you call its throttle()
faster than the normal thermal framework tick (due to interrupts for
example) as it will overreact.

Energy Model requirements
=========================

Another important thing is the consistent scale of the power values
provided by the cooling devices. All of the cooling devices in a single
thermal zone should have power values reported either in milli-Watts
or scaled to the same 'abstract scale'.